■ IEC62386-102(V1.0)/207通过测试内容
Test system firmware: v3.2
Test procedures: AG-DALI 1.1.0.1
Default test conditions: yes
High / low voltage: 16 V / 0 V
Rise / fall time: 50 µs / 50 µs
Current limit: 230 mA
IEC 62386-102 / 1.1.1 / Current rating
IEC 62386-102 / 1.1.2 / Voltage rating
IEC 62386-102 / 1.1.3 / Back channel rise time / fall time
IEC 62386-102 / 1.1.4 / Transmission rate
IEC 62386-102 / 1.1.5 / Pulse width
IEC 62386-102 / 1.1.6 / Code violation
IEC 62386-102 / 1.2 / Frame structure timing
IEC 62386-102 / 1.5 / Response Time
IEC 62386-102 / 2.1.1 / RESET
IEC 62386-102 / 2.1.2 / RESET: timeout / command in-between
IEC 62386-102 / 2.1.3 / 100 ms-timeout
IEC 62386-102 / 2.1.4 / Commands in-between
IEC 62386-102 / 2.1.5 / QUERY VERSION NUMBER
IEC 62386-102 / 2.1.6 / STORE ACTUAL LEVEL IN THE DTR
IEC 62386-102 / 2.1.7 / Persistent memory
IEC 62386-102 / 2.1.8 / DTR1
IEC 62386-102 / 2.1.9 / DTR2
IEC 62386-102 / 2.2.1 / STORE THE DTR AS MAX LEVEL
IEC 62386-102 / 2.2.2 / STORE THE DTR AS MIN LEVEL
IEC 62386-102 / 2.2.3 / STORE THE DTR AS SYSTEM FAILURE LEVEL
IEC 62386-102 / 2.2.4 / STORE THE DTR AS POWER ON LEVEL
IEC 62386-102 / 2.2.5 / STORE THE DTR AS FADE TIME
IEC 62386-102 / 2.2.6 / STORE THE DTR AS FADE RATE
IEC 62386-102 / 2.2.7 / STORE THE DTR AS SCENE / GO TO SCENE
IEC 62386-102 / 2.3.1 / REMOVE FROM SCENE
IEC 62386-102 / 2.3.2 / ADD TO GROUP / REMOVE FROM GROUP
IEC 62386-102 / 2.3.3 / STORE THE DTR AS SHORT ADDRESS
IEC 62386-102 / 2.4.1 / Memory Bank 0
IEC 62386-102 / 2.4.2 / Memory Bank 1
IEC 62386-102 / 2.4.3 / Other Memory Banks
IEC 62386-102 / 2.4.4 / ENABLE WRITE MEMORY
IEC 62386-102 / 3.1.1 / FADE TIME
IEC 62386-102 / 3.1.2 / FADE RATE
IEC 62386-102 / 3.2.1 / Logarithmic dimming curve
IEC 62386-102 / 3.2.2 / Dimming curve: DIRECT ARC POWER CONTROL
IEC 62386-102 / 3.2.3 / Dimming curve: UP / DOWN
IEC 62386-102 / 3.2.4 / Dimming curve: STEP UP / STEP DOWN
IEC 62386-102 / 3.2.5 / Dimming curve: DAPC SEQUENCE
IEC 62386-102 / 3.3.1 / OFF
IEC 62386-102 / 3.3.2 / DIRECT ARC POWER CONTROL
IEC 62386-102 / 3.3.3 / UP
IEC 62386-102 / 3.3.4 / DOWN
IEC 62386-102 / 3.3.5 / STEP UP
IEC 62386-102 / 3.3.6 / STEP DOWN
IEC 62386-102 / 3.3.7 / RECALL MAX LEVEL
IEC 62386-102 / 3.3.8 / RECALL MIN LEVEL
IEC 62386-102 / 3.3.9 / ON AND STEP UP
IEC 62386-102 / 3.3.10 / STEP DOWN AND OFF
IEC 62386-102 / 4 / Physical address allocation
IEC 62386-102 / 5.1.1 / INITIALISE: 15 minutes timer
IEC 62386-102 / 5.1.2 / TERMINATE
IEC 62386-102 / 5.1.3 / INITIALISE: short address
IEC 62386-102 / 5.1.4 / INITIALISE: no short address
IEC 62386-102 / 5.1.5 / INITIALISE: 100ms timeout
IEC 62386-102 / 5.1.6 / INITIALISE: command in-between
IEC 62386-102 / 5.2.1 / RANDOMISE: reset values
IEC 62386-102 / 5.2.2 / RANDOMISE: 100 ms timeout
IEC 62386-102 / 5.2.3 / RANDOMISE: command in-between
IEC 62386-102 / 5.3.1 / COMPARE
IEC 62386-102 / 5.3.2 / WITHDRAW
IEC 62386-102 / 5.4.1 / PROGRAM SHORT ADDRESS
IEC 62386-102 / 5.4.2 / VERIFY SHORT ADDRESS
IEC 62386-102 / 5.4.3 / QUERY SHORT ADDRESS
IEC 62386-102 / 5.4.4 / SEARCH ADDRESS: reset value
IEC 62386-102 / 6.1.1 / QUERY DEVICE TYPE
IEC 62386-102 / 6.1.2 / QUERY LAMP FAILURE
IEC 62386-102 / 6.1.3 / QUERY LAMP POWER ON
IEC 62386-102 / 6.1.4 / QUERY LIMIT ERROR
IEC 62386-102 / 6.1.5 / QUERY POWER FAILURE
IEC 62386-102 / 6.1.6 / QUERY STATUS: control gear ok
IEC 62386-102 / 6.1.7 / QUERY STATUS: fade running
IEC 62386-102 / 6.2.1 / RESERVED: standard commands
IEC 62386-102 / 6.2.2 / Application extended commands
IEC 62386-102 / 6.2.3 / RESERVED: special commands 1
IEC 62386-102 / 6.2.4 / RESERVED: special commands 2
IEC 62386-102 / 6.2.5 / Not supported device types
IEC 62386-207 / 7.1.1 / QUERY FEATURES
IEC 62386-207 / 7.1.2 / QUERY SHORT CIRCUIT
IEC 62386-207 / 7.1.4 / QUERY LOAD DECREASE
IEC 62386-207 / 7.1.5 / QUERY LOAD INCREASE
IEC 62386-207 / 7.1.6 / QUERY CURRENT PROTECTOR ACTIVE: Underload
IEC 62386-207 / 7.1.7 / QUERY CURRENT PROTECTOR ACTIVE: Overload
IEC 62386-207 / 7.1.8 / QUERY THERMAL SHUT DOWN
IEC 62386-207 / 7.1.9 / QUERY THERMAL OVERLOAD
IEC 62386-207 / 7.1.10 / Query control gear information
IEC 62386-207 / 7.2.1 / REFERENCE SYSTEM POWER
IEC 62386-207 / 7.2.2 / REFERENCE SYSTEM POWER: 100 ms-timeout
IEC 62386-207 / 7.2.3 / REFERENCE SYSTEM POWER: Command in-between
IEC 62386-207 / 7.2.4 / REFERENCE SYSTEM POWER: 15 minutes timer
IEC 62386-207 / 7.2.5 / REFERENCE SYSTEM POWER: failed
IEC 62386-207 / 7.2.6 / ENABLE / DISABLE CURRENT PROTECTOR
IEC 62386-207 / 7.2.7 / SELECT DIMMING CURVE
IEC 62386-207 / 7.2.8 / FAST FADE TIME
IEC 62386-207 / 7.2.9 / Reset State / Persistent Memory
IEC 62386-207 / 7.3.1 / ENABLE DEVICE TYPE: Application extended commands
IEC 62386-207 / 7.3.2 / ENABLE DEVICE TYPE: Application extended configuration commands 1
IEC 62386-207 / 7.3.3 / ENABLE DEVICE TYPE: Application extended configuration commands 2
IEC 62386-207 / 7.4.1 / QUERY EXTENDED VERSION NUMBER
IEC 62386-207 / 7.4.2 / RESERVED APPLICATION EXTENDED COMMANDS
■ IEC62386-102(V2.0)通过测试内容
IEC62386-102/2.1/Test preamble
IEC62386-102/3.1/Polarity test
IEC62386-102/3.2/Maximum and minimum system voltage
IEC62386-102/3.3/Overvoltage protection test
IEC62386-102/3.4/Current rating test
IEC62386-102/3.5/Transmitter voltages
IEC62386-102/3.6/Transmitter rising and falling edges
IEC62386-102/3.7/Transmitter bit timing
IEC62386-102/3.8/Transmitter frame timing
IEC62386-102/3.9/Receiver start-up behavior
IEC62386-102/3.10/Receiver threshold
IEC62386-102/3.11/Receiver bit timing
IEC62386-102/3.12/Extended receiver bit timing
IEC62386-102/3.13/Receiver forward frame violation
IEC62386-102/3.14/Receiver settling timing
IEC62386-102/3.15/Receiver frame timing FF-FF send twice
IEC62386-102/4.1/RESET
IEC62386-102/4.2/RESET: timeout / command in-between
IEC62386-102/4.3/Send twice timeout
IEC62386-102/4.4/Commands in-between
IEC62386-102/4.5/STORE ACTUAL LEVEL IN DTR0
IEC62386-102/4.6/SAVE PERSISTENT VARIABLES
IEC62386-102/4.7/SET OPERATING MODE
IEC62386-102/4.8/SET MAX LEVEL
IEC62386-102/4.9/SET MIN LEVEL
IEC62386-102/4.10/SET SYSTEM FAILURE LEVEL
IEC62386-102/4.11/SET POWER ON LEVEL
IEC62386-102/4.12/SET FADE TIME
IEC62386-102/4.13/SET FADE RATE
IEC62386-102/4.14/SET SCENE / REMOVE FROM SCENE
IEC62386-102/4.15/ADD TO GROUP / REMOVE FROM GROUP
IEC62386-102/4.16/SET SHORT ADDRESS
IEC62386-102/4.17/SET EXTEND FADE TIME
IEC62386-102/4.18/Reset/Power-on values
IEC62386-102/4.19/DTR0 / DTR1 / DTR2
IEC62386-102/5.1/READ MEMORY LOCATION on Memory Bank 0
IEC62386-102/5.2/READ MEMORY LOCATION on Memory Bank 1
IEC62386-102/5.3/READ MEMORY LOCATION on other Memory Banks
IEC62386-102/5.4/Memory bank writing
IEC62386-102/5.5/ENABLE WRITE MEMORY: writeEnableState
IEC62386-102/5.6/ENABLE WRITE MEMORY: timeout / command in-between
IEC62386-102/5.7/RESET MEMORY BANK: timeout / command in-between
IEC62386-102/5.8/RESET MEMORY BANK
IEC62386-102/6.1/Level instructions: Basic behaviour
IEC62386-102/6.2/FADE TIME: possible values
IEC62386-102/6.3/FADE TIME: transitions
IEC62386-102/6.4/FADE TIME: fading to 0
IEC62386-102/6.5/FADE TIME: small steps fading
IEC62386-102/6.6/FADE TIME: extended fade time
IEC62386-102/6.7/FADE RATE: possible values
IEC62386-102/6.8/FADE RATE: transitions
IEC62386-102/6.9/FADE RATE: extended fade time
IEC62386-102/6.10/FADE TIME/FADE RATE: stop fading by setting MIN/MAX levels
IEC62386-102/6.11/FADE TIME/FADE RATE: stop fading
IEC62386-102/6.12/FADE TIME/FADE RATE: stop fading when a command is sent, check timing
IEC62386-102/6.13/FADE TIME/FADE RATE: stop fading during startup
IEC62386-102/6.14/Level instructions: combined instructions
IEC62386-102/6.15/Power On Level – System Failure Level combined
IEC62386-102/6.16/ENABLE DAPC SEQUENCE
IEC62386-102/6.17/GO TO LAST ACTIVE LEVEL
IEC62386-102/6.18/GO TO SCENE
IEC62386-102/6.19/Power on: level control commands
IEC62386-102/6.20/Logarithmic dimming curve
IEC62386-102/6.21/Dimming curve: DAPC
IEC62386-102/6.22/Dimming curve: UP / DOWN
IEC62386-102/6.23/Dimming curve: STEP UP / STEP DOWN
IEC62386-102/6.24/FADE TIME/EXTENDED FADE TIME: light output behaviour
IEC62386-102/6.25/EXTENDED FADE TIME: light output behaviour
IEC62386-102/6.26/Behaviour during a fade
IEC62386-102/6.27/FADE TIME/FADE RATE: fading during startup
IEC62386-102/7.1/INITIALISE - timer
IEC62386-102/7.2/TERMINATE
IEC62386-102/7.3/INITIALISE – device addressing
IEC62386-102/7.4/RANDOMISE
IEC62386-102/7.5/COMPARE
IEC62386-102/7.6/WITHDRAW
IEC62386-102/7.7/SEARCHADDRH / SEARCHADDRM / EARCHADDRL
IEC62386-102/7.8/PROGRAM SHORT ADDRESS
IEC62386-102/7.9/VERIFY SHORT ADDRESS
IEC62386-102/7.10/QUERY SHORT ADDRESS
IEC62386-102/7.11/IDENTIFY DEVICE
IEC62386-102/7.12/IDENTFY DEVICE THROUCH RECALL MIN/MAX LEVEL
IEC62386-102/8.1/QUERY STATUS – lampFailure/lampOn
IEC62386-102/8.2/QUERY STATUS – lampOn
IEC62386-102/8.3/QUERY STATUS – limitError/lampOn
IEC62386-102/8.4/QUERY STATUS – powerCycleSeen
IEC62386-102/8.5/QUERY CONTROL GEAR PPRESENT
IEC62386-102/8.6/QUERY VERSION NUMBER
IEC62386-102/8.7/PING
IEC62386-102/8.8/Broadcast unaddressed
IEC62386-102/8.9/Reserved commands: standard commands
IEC62386-102/8.10/Reserved commands: special commands
IEC62386-102/8.11/Application extend commands
IEC62386-102/8.12/Not supported device types
IEC62386-102/8.13/Removed funcionality
IEC62386-102/9.1/DTR0
IEC62386-102/9.2/NVM variables
IEC62386-102/9.3/Random address generation
IEC62386-102/9.4/Addressing 1
IEC62386-102/9.5/Addressing 2
IEC62386-102/9.6/Addressing 3