DALI 2.0 完美兼容DALI 1.0 模块和电源

DALI 2.0 模块完美兼容DALI 1.0 模块,电源和模块都通过Probittab1&2的测试




深圳聚积智能科技开发有限公司

Add: 深圳市宝安区西乡镇固戍绵商大厦六楼

Tel:0755-36960722  Mobile:13246760327 Bruce

E-Mail:[email protected]


■ IEC62386-102(V1.0)/207通过测试内容

Test system firmware: v3.2

Test procedures: AG-DALI 1.1.0.1

Default test conditions: yes

High / low voltage: 16 V / 0 V

Rise / fall time: 50 µs / 50 µs

Current limit: 230 mA

IEC 62386-102 / 1.1.1 / Current rating

IEC 62386-102 / 1.1.2 / Voltage rating

IEC 62386-102 / 1.1.3 / Back channel rise time / fall time

IEC 62386-102 / 1.1.4 / Transmission rate

IEC 62386-102 / 1.1.5 / Pulse width

IEC 62386-102 / 1.1.6 / Code violation

IEC 62386-102 / 1.2 / Frame structure timing

IEC 62386-102 / 1.5 / Response Time

IEC 62386-102 / 2.1.1 / RESET

IEC 62386-102 / 2.1.2 / RESET: timeout / command in-between

IEC 62386-102 / 2.1.3 / 100 ms-timeout

IEC 62386-102 / 2.1.4 / Commands in-between

IEC 62386-102 / 2.1.5 / QUERY VERSION NUMBER

IEC 62386-102 / 2.1.6 / STORE ACTUAL LEVEL IN THE DTR

IEC 62386-102 / 2.1.7 / Persistent memory

IEC 62386-102 / 2.1.8 / DTR1

IEC 62386-102 / 2.1.9 / DTR2

IEC 62386-102 / 2.2.1 / STORE THE DTR AS MAX LEVEL

IEC 62386-102 / 2.2.2 / STORE THE DTR AS MIN LEVEL

IEC 62386-102 / 2.2.3 / STORE THE DTR AS SYSTEM FAILURE LEVEL

IEC 62386-102 / 2.2.4 / STORE THE DTR AS POWER ON LEVEL

IEC 62386-102 / 2.2.5 / STORE THE DTR AS FADE TIME

IEC 62386-102 / 2.2.6 / STORE THE DTR AS FADE RATE

IEC 62386-102 / 2.2.7 / STORE THE DTR AS SCENE / GO TO SCENE

IEC 62386-102 / 2.3.1 / REMOVE FROM SCENE

IEC 62386-102 / 2.3.2 / ADD TO GROUP / REMOVE FROM GROUP

IEC 62386-102 / 2.3.3 / STORE THE DTR AS SHORT ADDRESS

IEC 62386-102 / 2.4.1 / Memory Bank 0

IEC 62386-102 / 2.4.2 / Memory Bank 1

IEC 62386-102 / 2.4.3 / Other Memory Banks

IEC 62386-102 / 2.4.4 / ENABLE WRITE MEMORY

IEC 62386-102 / 3.1.1 / FADE TIME

IEC 62386-102 / 3.1.2 / FADE RATE

IEC 62386-102 / 3.2.1 / Logarithmic dimming curve

IEC 62386-102 / 3.2.2 / Dimming curve: DIRECT ARC POWER CONTROL

IEC 62386-102 / 3.2.3 / Dimming curve: UP / DOWN

IEC 62386-102 / 3.2.4 / Dimming curve: STEP UP / STEP DOWN

IEC 62386-102 / 3.2.5 / Dimming curve: DAPC SEQUENCE

IEC 62386-102 / 3.3.1 / OFF

IEC 62386-102 / 3.3.2 / DIRECT ARC POWER CONTROL

IEC 62386-102 / 3.3.3 / UP

IEC 62386-102 / 3.3.4 / DOWN

IEC 62386-102 / 3.3.5 / STEP UP

IEC 62386-102 / 3.3.6 / STEP DOWN

IEC 62386-102 / 3.3.7 / RECALL MAX LEVEL

IEC 62386-102 / 3.3.8 / RECALL MIN LEVEL

IEC 62386-102 / 3.3.9 / ON AND STEP UP

IEC 62386-102 / 3.3.10 / STEP DOWN AND OFF

IEC 62386-102 / 4 / Physical address allocation

IEC 62386-102 / 5.1.1 / INITIALISE: 15 minutes timer

IEC 62386-102 / 5.1.2 / TERMINATE

IEC 62386-102 / 5.1.3 / INITIALISE: short address

IEC 62386-102 / 5.1.4 / INITIALISE: no short address

IEC 62386-102 / 5.1.5 / INITIALISE: 100ms timeout

IEC 62386-102 / 5.1.6 / INITIALISE: command in-between

IEC 62386-102 / 5.2.1 / RANDOMISE: reset values

IEC 62386-102 / 5.2.2 / RANDOMISE: 100 ms timeout

IEC 62386-102 / 5.2.3 / RANDOMISE: command in-between

IEC 62386-102 / 5.3.1 / COMPARE

IEC 62386-102 / 5.3.2 / WITHDRAW

IEC 62386-102 / 5.4.1 / PROGRAM SHORT ADDRESS

IEC 62386-102 / 5.4.2 / VERIFY SHORT ADDRESS

IEC 62386-102 / 5.4.3 / QUERY SHORT ADDRESS

IEC 62386-102 / 5.4.4 / SEARCH ADDRESS: reset value

IEC 62386-102 / 6.1.1 / QUERY DEVICE TYPE

IEC 62386-102 / 6.1.2 / QUERY LAMP FAILURE

IEC 62386-102 / 6.1.3 / QUERY LAMP POWER ON

IEC 62386-102 / 6.1.4 / QUERY LIMIT ERROR

IEC 62386-102 / 6.1.5 / QUERY POWER FAILURE

IEC 62386-102 / 6.1.6 / QUERY STATUS: control gear ok

IEC 62386-102 / 6.1.7 / QUERY STATUS: fade running

IEC 62386-102 / 6.2.1 / RESERVED: standard commands

IEC 62386-102 / 6.2.2 / Application extended commands

IEC 62386-102 / 6.2.3 / RESERVED: special commands 1

IEC 62386-102 / 6.2.4 / RESERVED: special commands 2

IEC 62386-102 / 6.2.5 / Not supported device types

IEC 62386-207 / 7.1.1 / QUERY FEATURES

IEC 62386-207 / 7.1.2 / QUERY SHORT CIRCUIT

IEC 62386-207 / 7.1.4 / QUERY LOAD DECREASE

IEC 62386-207 / 7.1.5 / QUERY LOAD INCREASE

IEC 62386-207 / 7.1.6 / QUERY CURRENT PROTECTOR ACTIVE: Underload

IEC 62386-207 / 7.1.7 / QUERY CURRENT PROTECTOR ACTIVE: Overload

IEC 62386-207 / 7.1.8 / QUERY THERMAL SHUT DOWN

IEC 62386-207 / 7.1.9 / QUERY THERMAL OVERLOAD

IEC 62386-207 / 7.1.10 / Query control gear information

IEC 62386-207 / 7.2.1 / REFERENCE SYSTEM POWER

IEC 62386-207 / 7.2.2 / REFERENCE SYSTEM POWER: 100 ms-timeout

IEC 62386-207 / 7.2.3 / REFERENCE SYSTEM POWER: Command in-between

IEC 62386-207 / 7.2.4 / REFERENCE SYSTEM POWER: 15 minutes timer

IEC 62386-207 / 7.2.5 / REFERENCE SYSTEM POWER: failed

IEC 62386-207 / 7.2.6 / ENABLE / DISABLE CURRENT PROTECTOR

IEC 62386-207 / 7.2.7 / SELECT DIMMING CURVE

IEC 62386-207 / 7.2.8 / FAST FADE TIME

IEC 62386-207 / 7.2.9 / Reset State / Persistent Memory

IEC 62386-207 / 7.3.1 / ENABLE DEVICE TYPE: Application extended commands

IEC 62386-207 / 7.3.2 / ENABLE DEVICE TYPE: Application extended configuration commands 1

IEC 62386-207 / 7.3.3 / ENABLE DEVICE TYPE: Application extended configuration commands 2

IEC 62386-207 / 7.4.1 / QUERY EXTENDED VERSION NUMBER

IEC 62386-207 / 7.4.2 / RESERVED APPLICATION EXTENDED COMMANDS

■ IEC62386-102(V2.0)通过测试内容

IEC62386-102/2.1/Test preamble

IEC62386-102/3.1/Polarity test

IEC62386-102/3.2/Maximum and minimum system voltage

IEC62386-102/3.3/Overvoltage protection test

IEC62386-102/3.4/Current rating test

IEC62386-102/3.5/Transmitter voltages

IEC62386-102/3.6/Transmitter rising and falling edges

IEC62386-102/3.7/Transmitter bit timing

IEC62386-102/3.8/Transmitter frame timing

IEC62386-102/3.9/Receiver start-up behavior

IEC62386-102/3.10/Receiver threshold

IEC62386-102/3.11/Receiver bit timing

IEC62386-102/3.12/Extended receiver bit timing

IEC62386-102/3.13/Receiver forward frame violation

IEC62386-102/3.14/Receiver settling timing

IEC62386-102/3.15/Receiver frame timing FF-FF send twice

IEC62386-102/4.1/RESET

IEC62386-102/4.2/RESET: timeout / command in-between

IEC62386-102/4.3/Send twice timeout

IEC62386-102/4.4/Commands in-between

IEC62386-102/4.5/STORE ACTUAL LEVEL IN DTR0

IEC62386-102/4.6/SAVE PERSISTENT VARIABLES

IEC62386-102/4.7/SET OPERATING MODE

IEC62386-102/4.8/SET MAX LEVEL

IEC62386-102/4.9/SET MIN LEVEL

IEC62386-102/4.10/SET SYSTEM FAILURE LEVEL

IEC62386-102/4.11/SET POWER ON LEVEL

IEC62386-102/4.12/SET FADE TIME

IEC62386-102/4.13/SET FADE RATE

IEC62386-102/4.14/SET SCENE / REMOVE FROM SCENE

IEC62386-102/4.15/ADD TO GROUP / REMOVE FROM GROUP

IEC62386-102/4.16/SET SHORT ADDRESS

IEC62386-102/4.17/SET EXTEND FADE TIME

IEC62386-102/4.18/Reset/Power-on values

IEC62386-102/4.19/DTR0 / DTR1 / DTR2

IEC62386-102/5.1/READ MEMORY LOCATION on Memory Bank 0

IEC62386-102/5.2/READ MEMORY LOCATION on Memory Bank 1

IEC62386-102/5.3/READ MEMORY LOCATION on other Memory Banks

IEC62386-102/5.4/Memory bank writing

IEC62386-102/5.5/ENABLE WRITE MEMORY: writeEnableState

IEC62386-102/5.6/ENABLE WRITE MEMORY: timeout / command in-between

IEC62386-102/5.7/RESET MEMORY BANK: timeout / command in-between

IEC62386-102/5.8/RESET MEMORY BANK

IEC62386-102/6.1/Level instructions: Basic behaviour

IEC62386-102/6.2/FADE TIME: possible values

IEC62386-102/6.3/FADE TIME: transitions

IEC62386-102/6.4/FADE TIME: fading to 0

IEC62386-102/6.5/FADE TIME: small steps fading

IEC62386-102/6.6/FADE TIME: extended fade time

IEC62386-102/6.7/FADE RATE: possible values

IEC62386-102/6.8/FADE RATE: transitions

IEC62386-102/6.9/FADE RATE: extended fade time

IEC62386-102/6.10/FADE TIME/FADE RATE: stop fading by setting MIN/MAX levels

IEC62386-102/6.11/FADE TIME/FADE RATE: stop fading

IEC62386-102/6.12/FADE TIME/FADE RATE: stop fading when a command is sent, check timing

IEC62386-102/6.13/FADE TIME/FADE RATE: stop fading during startup

IEC62386-102/6.14/Level instructions: combined instructions

IEC62386-102/6.15/Power On Level – System Failure Level combined

IEC62386-102/6.16/ENABLE DAPC SEQUENCE

IEC62386-102/6.17/GO TO LAST ACTIVE LEVEL

IEC62386-102/6.18/GO TO SCENE

IEC62386-102/6.19/Power on: level control commands

IEC62386-102/6.20/Logarithmic dimming curve

IEC62386-102/6.21/Dimming curve: DAPC

IEC62386-102/6.22/Dimming curve: UP / DOWN

IEC62386-102/6.23/Dimming curve: STEP UP / STEP DOWN

IEC62386-102/6.24/FADE TIME/EXTENDED FADE TIME: light output behaviour

IEC62386-102/6.25/EXTENDED FADE TIME: light output behaviour

IEC62386-102/6.26/Behaviour during a fade

IEC62386-102/6.27/FADE TIME/FADE RATE: fading during startup

IEC62386-102/7.1/INITIALISE - timer

IEC62386-102/7.2/TERMINATE

IEC62386-102/7.3/INITIALISE – device addressing

IEC62386-102/7.4/RANDOMISE

IEC62386-102/7.5/COMPARE

IEC62386-102/7.6/WITHDRAW

IEC62386-102/7.7/SEARCHADDRH / SEARCHADDRM / EARCHADDRL

IEC62386-102/7.8/PROGRAM SHORT ADDRESS

IEC62386-102/7.9/VERIFY SHORT ADDRESS

IEC62386-102/7.10/QUERY SHORT ADDRESS

IEC62386-102/7.11/IDENTIFY DEVICE

IEC62386-102/7.12/IDENTFY DEVICE THROUCH RECALL MIN/MAX LEVEL

IEC62386-102/8.1/QUERY STATUS – lampFailure/lampOn

IEC62386-102/8.2/QUERY STATUS – lampOn

IEC62386-102/8.3/QUERY STATUS – limitError/lampOn

IEC62386-102/8.4/QUERY STATUS – powerCycleSeen

IEC62386-102/8.5/QUERY CONTROL GEAR PPRESENT

IEC62386-102/8.6/QUERY VERSION NUMBER

IEC62386-102/8.7/PING

IEC62386-102/8.8/Broadcast unaddressed

IEC62386-102/8.9/Reserved commands: standard commands

IEC62386-102/8.10/Reserved commands: special commands

IEC62386-102/8.11/Application extend commands

IEC62386-102/8.12/Not supported device types

IEC62386-102/8.13/Removed funcionality

IEC62386-102/9.1/DTR0

IEC62386-102/9.2/NVM variables

IEC62386-102/9.3/Random address generation

IEC62386-102/9.4/Addressing 1

IEC62386-102/9.5/Addressing 2

IEC62386-102/9.6/Addressing 3